The Riello GAS/2 series is a range of two-stage forced-draught gas burners that covers 130 to 3,200 kW in six models, from the GAS 3/2 to the GAS 9/2. They burn natural gas or LPG and suit steam boilers, hot-water boilers, thermic fluid heaters, ovens and furnaces. Combustion & Control Systems in Vasai, Mumbai supplies all six models with gas trains and spares across India.

Riello GAS 3/2 to GAS 9/2 output table
| Model | 1st stage (low fire) | 2nd stage (full fire) |
|---|---|---|
| Riello GAS 3/2 | 80 kW | 130–350 kW |
| Riello GAS 4/2 | 120 kW | 180–470 kW |
| Riello GAS 5/2 | 155 kW | 320–660 kW |
| Riello GAS 6/2 | 300 kW | 520–1,050 kW |
| Riello GAS 7/2 | 400 kW | 800–1,760 kW |
| Riello GAS 9/2 | 1,000 kW | 1,750–3,200 kW |
Figures are from Riello’s GAS/2 technical data sheet, tested to EN 676. The 1st-stage figure is the minimum low-fire output; the 2nd-stage range is the full-fire output you choose the burner by.
What does “two-stage” mean?
A two-stage burner has two firing rates: low fire and high fire. It starts on low fire, which gives a softer, safer ignition, then moves to high fire when the boiler needs more heat. When the demand drops, it goes back to low fire instead of switching off. As a result, there are fewer on/off cycles, steadier steam pressure or temperature, and less wear on the burner and boiler.
- Single-stage (on/off): simple and cheaper, fine for small, steady loads such as an oven. Example: Riello 40 FS10.
- Two-stage: better for boilers whose load changes during the day. Example: the Riello GAS/2 series.
- Modulating: follows the load smoothly and needs extra controls. Ask us if your plant needs it.
How to choose a Riello two-stage gas burner
- Find the boiler’s heat input in kW on its name plate. If it is in kcal/h, divide by 860 to get kW.
- Pick the model whose 2nd-stage range includes that figure. For example, a 600 kW boiler fits the GAS 5/2 (320–660 kW).
- Check your gas pressure and gas type (natural gas or LPG). The gas train size depends on these.
- Check the combustion chamber: back-pressure and furnace length affect the final choice.
Our Riello burner sizing guide goes through this with examples. Or simply WhatsApp us a photo of the boiler name plate.
Where is a Riello two-stage gas burner used?
- Steam boilers in textile, food, dairy and pharma plants
- Hot-water boilers for hotels, hospitals and buildings
- Thermic fluid heaters
- Industrial ovens, dryers and process furnaces
Gas train and installation
Every GAS/2 burner needs a gas train: manual valve, filter, pressure regulator, pressure switches and safety solenoid valves, sized for your gas pressure and burner output. Read how a Riello gas train works and Riello gas burner installation basics. For upkeep, use our gas burner maintenance checklist.
Frequently asked questions
What is the output range of the Riello GAS/2 series?
About 130 to 3,200 kW at full fire, across six models from the GAS 3/2 to the GAS 9/2.
Which Riello GAS/2 model is the smallest?
The GAS 3/2, with a full-fire range of 130–350 kW and a minimum low-fire output of 80 kW.
Can the GAS/2 burners run on LPG?
Riello GAS burners are built for gaseous fuels. Tell us whether you use natural gas or LPG so we can confirm the right version and gas train.
Which is better for a boiler, single-stage or two-stage?
For a boiler whose heat demand changes during the day, a two-stage burner gives steadier pressure and fewer start-stops. Small ovens and steady loads can use a single-stage burner.