Siemens LME22.331C2 burner controls
Approx. Original price was: ₹8,000.00.₹7,250.00Current price is: ₹7,250.00. (+ GST, freight extra)
Siemens LME22.331C2 two-stage burner control box for gas and gas/oil burners: ionization, 30 s pre-purge, 3 s safety time, 12 s actuator time, AC 230 V. Replaces LGB22.330A27 and LMG22.330B27. WhatsApp +91 98197 08885.
Product description
The Siemens LME22.331C2 is a two-stage burner control box for forced-draught gas burners and gas/oil dual-fuel burners with ionization flame detection. It runs on AC 230 V with a 30-second pre-purge, a 3-second safety time and a 12-second air-damper actuator running time. Combustion & Control Systems in Vasai, Mumbai supplies it across India.
Ask price and availability on WhatsApp: +91 98197 08885
Siemens LME22.331C2 technical specifications
| Part code | LME22.331C2 |
|---|---|
| Manufacturer | Siemens |
| Type | Burner control (flame safeguard), LME family |
| Burner operation | Two-stage (or modulating with external controller) |
| Fuel | Gas, or gas/oil dual-fuel burners |
| Flame detection | Ionization probe |
| Pre-purge time (t1) | 30 s |
| Safety time (TSA) | 3 s |
| Actuator running time | 12 s |
| Supply voltage | AC 230 V |
What does the LME22.331C2 replace?
The LME22 is the Siemens successor for older two-stage gas burner controls:
- Siemens LGB22.330A27
- Siemens LMG22.330B27
For single-stage gas burners, use the Siemens LME11.330C2 instead.
How the LME22 works
On a heat demand, the LME22 drives the air damper actuator open for pre-purge, closes it to the low-fire position, switches on ignition and opens the first-stage gas valve. Once the ionization probe proves the flame, it releases the second stage. If the flame is not proved within 3 seconds, or is lost during operation, it shuts the gas valves and locks out.
Common LME22 lockout causes
- Low ionization current: dirty or misplaced probe, poor earth, or phase and neutral swapped.
- No ignition spark at the electrodes.
- Air pressure switch not proving during pre-purge.
- Actuator not reaching its end switches within the running time.
- Low gas pressure or faulty gas pressure switch.
Buy Siemens LME22.331C2 in Mumbai
Combustion & Control Systems has supplied burner spares since 1996. Address: Gala No. 204, B Block, Prime Trade Center, Waliv Phata, Sativali Road, Vasai (E) – 401208, Maharashtra. We dispatch across India.
WhatsApp +91 98197 08885 for price
Frequently asked questions
What is the difference between LME11 and LME22?
The LME11 is for single-stage gas burners. The LME22 is for two-stage burners and also controls an air damper actuator.
Can the LME22.331C2 be used on an oil burner?
It is used on gas burners and on gas/oil dual-fuel burners with ionization detection. Light-oil-only burners normally use an LMO control with a photocell.
What is the safety time of the LME22.331C2?
3 seconds, with a 30-second pre-purge.
Does the price include the base?
The base is usually a separate part. Tell us if you need it when you ask for a price.
Request a quotation
Enquiry for: Siemens LME22.331C2 burner controls