Siemens LME11.330C2 Burner Control Box
Approx. Original price was: ₹6,000.00.₹5,250.00Current price is: ₹5,250.00. (+ GST, freight extra)
Siemens LME11.330C2 single-stage burner control box for gas burners: ionization flame detection, 30 s pre-purge, 3 s safety time, AC 230 V. Fits Ecoflam Max Gas, Baltur and Bentone gas burners. WhatsApp +91 98197 08885 for price.
Product description
The Siemens LME11.330C2 is a single-stage burner control box (flame safeguard) for forced-draught gas burners with ionization flame detection. It runs on AC 230 V with a 30-second pre-purge (t1) and a 3-second safety time (TSA). Combustion & Control Systems in Vasai, Mumbai supplies it for burner OEMs and maintenance teams across India.
Ask price and availability on WhatsApp: +91 98197 08885
Siemens LME11.330C2 technical specifications
| Part code | LME11.330C2 |
|---|---|
| Manufacturer | Siemens |
| Type | Burner control (flame safeguard), LME family |
| Burner operation | Single-stage |
| Flame detection | Ionization probe |
| Pre-purge time (t1) | 30 s |
| Safety time (TSA) | 3 s |
| Supply voltage | AC 230 V |
Which burners use the LME11.330C2?
The LME11.330C2 and its LME11 variants are fitted on many single-stage forced-draught gas burners, including:
- Ecoflam Max Gas range (Max Gas 40 to 500)
- Baltur single-stage gas burners
- Bentone gas burners (for example the STG146)
- Burners that originally used the Riello RMG88.62C2 control box
Always match the full part code printed on the label of your old control box before ordering. Send us a photo of the label on WhatsApp and we will confirm the correct replacement.
What does the LME11.330C2 do?
The control box runs the burner start-up sequence: it starts the fan for pre-purge, switches on the ignition, opens the gas valve and checks for a flame signal from the ionization probe. If no flame is detected within the 3-second safety time, it shuts the gas valve and goes to lockout. It also locks out if the flame is lost during operation, protecting the boiler, furnace or heater.
Common LME11 lockout causes
- Weak or no ionization signal: dirty, cracked or badly positioned ionization probe, or poor burner earth.
- No ignition spark: worn electrodes, faulty ignition transformer or HT cable.
- Gas supply problem: low gas pressure, closed valve, or a faulty gas pressure switch.
- Air pressure switch not changing over during pre-purge.
- Phase and neutral reversed on the supply, which stops ionization detection.
Press the reset button once. If the burner locks out again, find the cause before resetting repeatedly.
Buy Siemens LME11.330C2 in Mumbai
Combustion & Control Systems has supplied burner spares since 1996. Visit or contact us at Gala No. 204, B Block, Prime Trade Center, Waliv Phata, Sativali Road, Vasai (E) – 401208, Maharashtra. We dispatch across India.
WhatsApp +91 98197 08885 for price
Frequently asked questions
Is the LME11.330C2 for gas or oil burners?
It is for gas burners. It uses ionization flame detection, which is used on gas burners. Oil burners use the LMO family (for example the LMO14 or LMO24) with a photocell.
What is the safety time of the LME11.330C2?
The safety time (TSA) is 3 seconds and the pre-purge time (t1) is 30 seconds.
Can the LME11.330C2 run a two-stage burner?
No. The LME11 is for single-stage burners. Two-stage gas burners use the LME22 family, such as the LME22.331C2.
Does the control box come with the base?
The base (plug-in socket) is usually a separate part. Tell us whether you need the base when you ask for a price.